Grease trap sizing: the formulas and minimum sizes Texas cities publish
Last updated .
How grease traps and interceptors are sized, using only methods that cities publish themselves: Austin’s fixture-unit formula, the Uniform Plumbing Code meals-per-hour worksheet used by Fort Worth, Southlake and Irving, and North Richland Hills’ peak-flow rule. It also covers each city’s minimum size, disposals and dishwashers, hydromechanical units, and what to get approved before you buy. Every rule links to its source.
How is a grease trap sized?
Your sewer authority decides, using one of three published methods. Austin counts fixture units, multiplies by 3 gallons per minute, then by 12 minutes. Fort Worth, Southlake and Irving use the Uniform Plumbing Code meals-per-hour formula. North Richland Hills multiplies peak drain flow by 30 minutes. Every city then applies its own minimum size.
This page does not size your trap. Your sewer authority’s approval sets the size. The worked examples below either come from a city document, or are labeled as our own arithmetic with made-up inputs, to show how a published formula works. This is not engineering or legal advice.
The three published sizing methods
| Method | Formula | Who publishes it |
|---|---|---|
| Fixture units | Total fixture units × 3 gallons per minute = flow rating; flow rating × 12 minutes = minimum liquid capacity in gallons.[1] | Austin (Austin Water Industrial Waste). |
| Meals per hour (Uniform Plumbing Code, Appendix H) | Meals per peak hour × waste flow rate × retention time × storage factor = liquid capacity in gallons.[2][3] | Fort Worth (its “Method 1”), Southlake (its sizing worksheet) and Irving, whose code says gravity interceptors are sized with a meals-per-hour method.[2][6][7] |
| Peak drain flow | Peak drain flow into the interceptor in gallons per minute × 30 minutes retention = gravity interceptor capacity.[5] | North Richland Hills, under city ordinance and the 2024 International Plumbing Code.[5] |
Other cities on this site point to a plumbing code instead of printing a formula. Grand Prairie sizes the interceptor from the total flow rate of three-compartment sinks, prep sinks and dishwashers under the International Plumbing Code, and links a sizing requirements sheet.[8] Dallas follows the Dallas Plumbing Code sizing criteria and sends sizing questions to its Plumbing and Mechanical Section.[9] Irving’s ordinance also requires the unit to receive peak flow and meet International Plumbing Code Sections 1003.3.2 through 1003.3.7 and Table 1003.3.5.1.[7] New Orleans and San Antonio rules are on grease trap vs. grease interceptor.
Austin’s fixture-unit method
- Count fixture units. For fixtures draining through a floor sink or hub drain, one-, two- and three-compartment sinks and wok stoves count 4, 6 or 8 for a 2-, 3- or 4-inch trap arm; a dishwasher counts 6 or 8; hand sinks and mop sinks count 2, 3 or 4. Directly connected hand sinks count 0, and floor drains and mop sinks count 2, 3 or 4. Trench drains that receive grease count 4, 6 or 8.[1]
- Flow rating = total fixture units × 3 gallons per minute.[1]
- Minimum liquid holding capacity = flow rating × 12 minutes.[1]
Austin’s conditions: for indirect waste systems where floor sinks and hub drains receive dishwashers and compartment sinks, the fixture-unit count is twice the floor sink or hub drain count. Clear-water fixtures, such as cooler condensate, may drain through the trap but are not counted unless routed to a floor sink. Kitchens with dishwashers or wok stoves need two compartments and 12 minutes total retention. Staff apply the formula with professional judgment and often require a larger trap.[1] The full fixture table is on Austin Water’s page and summarized on our interceptor page.
What is the Uniform Plumbing Code grease interceptor sizing formula?
Multiply meals per peak hour by the waste flow rate, the retention time and a storage factor. Meals per peak hour is seats times a meal factor, 1.33 for fast food and 1.00 for a restaurant. Flow is 6 gallons with a dishwasher, 5 without, 2 for single service. Retention is 2.5 or 1.5 hours.
| Factor | Fort Worth guidance (2018) | Southlake worksheet |
|---|---|---|
| Meals per peak hour | Seating capacity × peak factor: 1.33 fast food, 1.00 all other food service.[2] | Seating capacity × meal factor: fast food (45 min) 1.33, restaurant (60 min) 1.00, leisure dining (90 min) 0.67, dinner club (120 min) 0.50.[3] |
| Waste flow rate | With dishwasher 6 gallons; without 5; single service kitchen 2; food waste disposer 1.[2] | Same four values (disposer row reads “food waste disposer only”).[3] |
| Retention time | Commercial kitchen waste or dishwasher 2.5 hours; single service kitchen 1.5 hours.[2] | Same.[3] |
| Storage factor | Fully equipped kitchen: 8-hour operation 1, 16-hour 2, 24-hour 3; single service 1.5.[2] | 8 hours 1.00, 12 hours 1.50, 16 hours 2.00, 24 hours 3.00; single service 1.50.[3] |
Fort Worth defines a single service kitchen as one with a three-compartment sink, hand sink and mop sink that uses disposable cups, plates and utensils. It says the code’s built-in safety factor can produce very large sizes, that it is not currently requiring traps larger than 4,000 gallons, and that a smaller-than-formula trap must be justified in the plan submission. A Texas licensed professional engineer may submit an alternative method with sealed plans.[2] Southlake’s worksheet ends with picking a manufacturer’s size at or above the calculated capacity, and carries an engineer’s certification line.[3]
What does a worked grease interceptor sizing example look like?
Irving’s published example is a 120-seat full-service restaurant with a dishwasher, open 16 hours. 120 meals per hour times 6 gallons is 720 gallons per hour; times 2.5 hours is 1,800 gallons; times a storage factor of 2.0 is 3,600 gallons. Irving selected a 4,000-gallon interceptor for a 90-day pumping interval.
Source [4]
| Step | Irving’s published example | Our arithmetic, made-up fast-food shop |
|---|---|---|
| Kitchen | 120 seats, dishwasher, open 16 hours | 40 seats, single service (disposables, no dishwasher), open 12 hours |
| Meals per peak hour | 120 × 1.0 = 120 | 40 × 1.33 = 53.2 |
| × waste flow | × 6 gal = 720 gal/hour | × 2 gal = 106.4 gal/hour |
| × retention | × 2.5 hours = 1,800 gal | × 1.5 hours = 159.6 gal |
| × storage factor | × 2.0 = 3,600 gal | × 1.5 (single service) = about 239 gal |
| Result | Irving selected a 4,000-gallon interceptor. | Below Southlake’s 300-gallon floor, so 300 there; Fort Worth would still recommend 750 and never accept an exterior trap under 500. |
Irving’s column is quoted from its sizing examples, which use 2.5 hours of detention and say the volume keeps grease and solids under 25 percent of the wetted depth within a 90-day service interval.[4] The right column is our own illustration with invented inputs and the factors from Southlake’s worksheet; the minimums come from Southlake and Fort Worth.[3][6][2] Using Austin’s method instead, a made-up kitchen with 20 fixture units would need 20 × 3 = 60 gallons per minute and 60 × 12 = 720 gallons; with a dishwasher, Austin’s 500-gallon minimum would apply if the formula gave less.[1]
North Richland Hills’ peak-flow method
North Richland Hills sizes interceptors on the total potential flow from every fixture and drain in food preparation, handling, serving and clean-up areas. A gravity interceptor’s capacity is peak drain flow in gallons per minute times a 30-minute retention time; for example, 60 gallons per minute would mean 1,800 gallons (our arithmetic). Every interceptor must be outside the building; under-sink units are not allowed.[5]
What is the minimum grease interceptor size?
It depends on the city. Austin approves nothing under 100 gallons and requires 500 with a dishwasher. Southlake’s smallest gravity interceptor is 300 gallons. Fort Worth recommends at least 750 gallons for restaurants and never accepts an exterior trap under 500. North Richland Hills requires 300 gallons with a disposal or flow over 50 gallons per minute.
| City | Minimum | Other size rules |
|---|---|---|
| Austin, TX | 100 gallons liquid capacity; 500 gallons for kitchens with a dishwasher.[1] | Size and design come in the Industrial Waste approval letter.[1] |
| Fort Worth, TX | 750 gallons recommended for restaurants when formulas give less; exterior traps never under 500 gallons.[2] | Double the calculated size with garbage disposals; not currently requiring more than 4,000 gallons.[2] |
| Southlake, TX | 300 gallons for a gravity interceptor.[6] | Sized with the city’s UPC worksheet.[3] |
| North Richland Hills, TX | 300 gallons with a food disposal or more than 50 gallons per minute of discharge; at least a 100-pound trap at 50 gallons per minute or less.[5] | Those are floors; the actual size follows total potential fixture flow.[5] |
| Irving, TX | Size and type approved by the director.[7] | Published example uses 2.5 hours detention and a 90-day storage basis.[4] |
| New Orleans, LA | Dishwashers with booster heaters or water above 140 °F may not drain through a unit smaller than 1,000 gallons.[10] | Sized under the International Plumbing Code; see other city rules.[10] |
How do garbage disposals affect grease trap size?
They make the trap bigger or are not allowed at all. Austin has prohibited garbage disposals and grinders in commercial kitchens since January 2008. North Richland Hills says a food waste disposer may not discharge to a grease interceptor. Fort Worth requires an interceptor twice the calculated size for kitchens with garbage disposals.
- Dishwashers. Austin requires at least 500 gallons and two compartments with 12 minutes of retention when a dishwasher drains to the trap.[1] In the meals formula a dishwasher raises the flow rate from 5 to 6 gallons per meal.[2]
- Hot water. Fort Worth wants traps at least 10 feet from sinks and dishwashers so wastewater cools, and water under 120 °F before it enters the trap.[2]
- Drains to include. Fort Worth says every grease-bearing stream goes through the trap, including three-compartment and pot sinks, soup kettles, hand sinks, dishwashers, mop sinks and floor drains.[2] Austin says hand sinks don’t have to be plumbed to the trap.[1] Follow your own city’s rule.
How is a hydromechanical grease interceptor sized?
By flow rate, not by meals. Austin requires ASME A112.14.3 certification, a rating of at least 75 gallons per minute and a Type D installation. North Richland Hills sizes them by the manufacturer’s recommendation and International Plumbing Code Table 1003.3.5.1. Southlake encourages them only where there is minimal or no cooking on site.
Austin says hydromechanical units generally suit low-grease shops such as small sandwich shops, coffee shops and bakeries that use disposable flatware and no automatic dishwasher.[1] North Richland Hills warns that many hydromechanical units won’t meet its minimum sizes, often need a flow control device, and may need to sit within 25 feet of the fixtures, which can mean several units.[5] Southlake will not approve one if the kitchen needs a dishwasher or garbage disposal; it requires a gravity interceptor instead, and may require one later if the menu or fixtures change.[6] How the two types differ: gravity vs. hydromechanical.
Can I buy a grease trap before the city approves the size?
No. Get the size in writing first. Austin says not to buy a trap until building plan approval and an Industrial Waste approval letter specify the size and design. Irving requires the director to approve the size and type, and Fort Worth reviews size during plan review. A licensed plumber or engineer usually prepares the calculation.
- Get the approved size and design in writing (Austin: the Industrial Waste approval letter).[1]
- Have a licensed plumber or engineer prepare drawings and flow calculations if your city asks for them; Irving does.[7]
- Moving into a space with an existing interceptor? North Richland Hills says you may need to replace it if it is in poor condition, grossly undersized by current standards, or new fixtures need more capacity.[5] Southlake requires an existing interceptor to be pumped and power-washed for inspection when a new food business moves in.[11]
- A correctly sized trap still has to be pumped on the city schedule, usually at least every 90 days; see grease trap maintenance.
Related pages
Types and definitions: grease trap vs. grease interceptor. Upkeep: grease trap maintenance. Schedules and costs: the grease trap cleaning guide. Inspections: grease trap inspections. City rules and officially listed haulers: all cities. Rules change, so confirm with your sewer authority before you design or buy.
Sources
Sources checked .
- Austin Water, Grease Trap Sizing & Design Criteria (interceptor policies updated April 2021; page checked October 29, 2026)
- Fort Worth Water Pretreatment Services, Guidance Document for Sizing and Installation of Grease Traps and Interceptors (PDF, 2018)
- City of Southlake Public Works, Grease Interceptor Sizing Worksheet (UPC meals × flow × retention × storage; DocumentCenter View/42567; PDF created Dec. 13, 2024)
- City of Irving, Grease Interceptor Sizing Examples (GGI; detention time 2.5 hours; pump at least every 90 days or at 25% FOG + solids)
- City of North Richland Hills Planning and Development, Grease Interceptor Questions and Requirements (DocumentCenter View/21965)
- City of Southlake Public Works, Fats, Oils, and Grease (FOG) Manual (Adopted Jan. 2013; Revised Jan. 2020; DocumentCenter View/44323 FOG-MANUAL-June-2025; PDF modified June 13, 2025)
- City of Irving Ordinance ORD-2025-11144 amending Chapter 41 Water and Sewer Systems, Article VIII Liquid Waste Transport and Management (adopted 2025; Sec. 41-50 grease trap/interceptor duties)
- City of Grand Prairie Public Health and Environmental Quality, Grease Traps page (food service permits)
- Dallas Water Utilities, Pretreatment Program frequently asked questions
- Sewerage & Water Board of New Orleans, Plumbing Code Section 16.5, Rules Governing the Discharge into the Public Sanitary Sewerage System From Grease Traps and Grease Interceptors (PDF, February 2016 version linked from the S&WB pretreatment page)
- City of Southlake Building Inspections, Commercial Submittal Guidelines April 2026 (existing grease interceptors must be pumped and power-washed for Public Works inspection at move-in)